„Aquarea High Performance All in One J Generation 1 Phase“ • R32 |
SINGLE PHASE (Power to indoor) |
|
9 kW |
Kit |
KIT-ADC09JE5-1 |
Heating capacity (A +7°C, W 35°C) |
kW |
9 |
COP (A +7°C, W 35°C) |
4,48 |
Heating capacity (A +7°C, W 55°C) |
kW |
8,95 |
COP (A +7°C, W 55°C) |
2,78 |
Heating capacity (A +2°C, W 35°C) |
kW |
7 |
COP (A +2°C, W 35°C) |
3,4 |
Heating capacity (A +2°C, W 55°C) |
kW |
6,3 |
COP (A +2°C, W 55°C) |
2,16 |
Heating capacity (A -7°C, W 35°C) |
kW |
6,12 |
COP (A -7°C, W 35°C) |
2,78 |
Heating capacity (A -7°C, W 55°C) |
kW |
5,9 |
COP (A -7°C, W 55°C) |
1,93 |
Cooling capacity (A 35°C, W 7°C) |
kW |
8,2 |
EER (At 35°C, W 7°C) |
2,72 |
Cooling capacity (A 35°C, W 18°C) |
kW |
9 |
EER (At 35°C, W 18°C) |
4,18 |
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) |
ηs % |
193 / 130 |
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) |
SCOP |
4,90 / 3,32 |
Heating average climate. Energy class (W 35°C / W 55°C) (1) |
A+++ to D |
A+++ / A++ |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) |
ηs % |
227 / 160 |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) |
SCOP |
5,75 / 4,07 |
Heating warm climate. Energy class (W 35°C / W 55°C) (1) |
A+++ to D |
A+++ / A+++ |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) |
ηs % |
164 / 116 |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) |
SCOP |
4,18 / 2,98 |
Heating cold climate. Energy class (W 35°C / W 55°C) (1) |
A+++ to D |
A++ / A+ |
Indoor unit |
WH-ADC0309J3E5 |
Indoor sound pressure (Heat) |
dB(A) |
28 |
Indoor sound pressure (Cool) |
dB(A) |
28 |
Indoor dimension (Height) |
mm |
1800 |
Indoor dimension (Width) |
mm |
598 |
Indoor dimension (Depth) |
mm |
717 |
Indoor net weight |
kg |
122 |
Water pipe connector |
Inch |
R 1¼ |
A class pump (Number of speeds) |
Variable Speed |
A class pump (Input power Min) |
W |
30 |
A class pump (Input power Max) |
W |
120 |
Heating water flow (∆T=5 K. 35°C) |
L/min |
25,8 |
Capacity of integrated electric heater |
kW |
3 |
Indoor recommended fuse |
A |
25 / 16 |
Recommended cable size, supply 1 |
mm² |
3 x 2,5 |
Recommended cable size, supply 2 |
mm² |
3 x 1,5 |
Water volume |
L |
185 |
Maximum water temperature |
°C |
65 |
Material inside tank |
Stainless steel |
Tapping profile according EN16147 |
L |
DHW tank ERP average climate efficiency rating (2) |
A+ to F |
A+ |
DHW tank ERP warm climate efficiency rating (2) |
A+ to F |
A+ |
DHW tank ERP cold climate efficiency rating (2) |
A+ to F |
A |
DHW tank ERP average climate η |
ηwh % |
120 |
DHW tank ERP average climate SCOP |
3 |
DHW tank ERP warm climate η |
ηwh % |
140 |
DHW tank ERP warm climate SCOP |
3,5 |
DHW tank ERP cold climate η |
ηwh % |
99 |
DHW tank ERP cold climate SCOP |
2,47 |
Outdoor unit |
WH-UD09JE5-1 |
Outdoor sound power part load (Heat) (3) |
dB(A) |
59 |
Outdoor sound power full load (Heat) |
dB(A) |
69 |
Outdoor sound power full load (Cool) |
dB(A) |
69 |
Outdoor dimension (Height) |
mm |
795 |
Outdoor dimension (Width) |
mm |
875 |
Outdoor dimension (Depth) |
mm |
320 |
Outdoor net weight |
kg |
61 |
Refrigerant (R32) / CO2 Eq. |
kg / T |
1,27 / 0,857 |
Pipe diameter (Liquid) |
Inch (mm) |
1/4 (6,35) |
Pipe diameter (Gas) |
Inch (mm) |
5/8 (15,88) |
Pipe length range |
m |
3 ~ 50 |
Elevation difference (in/out) |
m |
30 |
Pipe length for additional gas |
m |
10 |
Additional gas amount |
g/m |
25 |
Operation range (Outdoor ambient) |
°C |
-20 ~ +35 |
Water outlet (Heat) |
°C |
20 ~ 60 |
Water outlet (Cool) |
°C |
5 ~ 20 |
|
Reviews